2.6 First commissioning control mode vector U/f in booksize format
What to do?
3.1
Line contactor
3.2
Enable Motor
Module
94
Line contactor
p0728.8 = 1 Set DI/DO as output
p0738 = 863.1 Activate line contactor
p0860 = 723.9 Line contactor, feedback signal
Enable signals for the Motor Module (drive_1)
p0840 = 722.0 ON/OFF1
p0844 = 722.1 1. OFF2
p0845 = 1 2. OFF2
p0848 = 722.2 1. OFF3
p0849 = 1 2. OFF3
p0852 = 722.3 Enable operation
How to do it?
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Comment
The line contactor must be
controlled by the
Einspeisung_1 drive object.
The inputs/outputs are
located on the Control Unit.
See the function diagram
[8934]
See function diagram
[2501]