User-Programmable Inverse-Time Characteristics - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
11.2.1.2
11.2.1.3
REX640
Technical Manual

User-programmable inverse-time characteristics

The user can define curves by entering parameters into the following standard
formula:
A
t s
B k
[ ]
=
+
c
I
E
 −
I
>
GUID-5C2959BE-F341-463F-B203-AB840575BDBB V1 EN
t[s] Operate time (in seconds)
Curve parameter A
A
Set
Curve parameter B
B
Set
Curve parameter C
C
Set
Curve parameter E
E
Set
I
Measured current
Start value
I>
Set
Time multiplier
k
Set
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is an
earth-fault specific characteristic.
The RI-type is calculated using the formula
k
t s
[ ]
=
I
>
0 339 0 236
.
.
I
GUID-D4289E23-1A3C-4A5D-9A46-A3596F1ECF42 V1 EN
The RD-type is calculated using the formula
I
t s
5 8 1 35 In
[ ]
.
.
=
k I
⋅ >
GUID-7B2D3993-7C18-473C-AA94-B0010E66EA77 V1 EN
General function block features
Section 11
(Equation 355)
(Equation 356)
(Equation 357)