Section 8
Measurement functions
8.1.4.4
8.1.4.5
1298

Analog channel configuration

CMMXU has one analog group input which must be properly configured.
Table 1214:
Analog inputs
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.
Signals
Table 1215:
CMMXU Input signals
Name
Type
I3P
SIGNAL
BLOCK
BOOLEAN
Table 1216:
CMMXU Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
I_INST_A
FLOAT32
I_INST_B
FLOAT32
I_INST_C
FLOAT32
I_DMD_A
FLOAT32
I_DMD_B
FLOAT32
I_DMD_C
FLOAT32
Description
Three-phase currents
Default
Description
-
Three-phase currents
0=False
Block signal for all binary outputs
Description
High alarm
High warning
Low warning
Low alarm
Phase A current instantaneous value amplitude in
amperes
Phase B current instantaneous value amplitude in
amperes
Phase C current instantaneous value amplitude in
amperes
Demand value of IL1 current
Demand value of IL2 current
Demand value of IL3 current
1MRS759142 C