Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.7.1.11
920
Name
Type
Flt loop 2nd Rea Zn4
FLOAT32
Flt PP-loop Ris Zn4
FLOAT32
Flt PP-loop Rea Zn4
FLOAT32
Phase reactance Zn4
FLOAT32
Fault/load Dir Zn5
Enum
Dir resistance Zn5
FLOAT32
Dir reactance Zn5
FLOAT32
Flt loop 1st Ris Zn5
FLOAT32
Flt loop 1st Rea Zn5
FLOAT32
Flt loop 2nd Ris Zn5
FLOAT32
Flt loop 2nd Rea Zn5
FLOAT32
Flt PP-loop Ris Zn5
FLOAT32
Flt PP-loop Rea Zn5
FLOAT32
Phase reactance Zn5
FLOAT32

Technical data

Table 855:
DSTPDIS Technical data
Characteristic
Operation accuracy
1)
Shortest operate time
SIR
Transient overreach SIR = 0.1...50
Table continues on next page
Values (Range)
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
0=unknown
1=forward
2=backward
3=both
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
-3000.00...3000.
00
Value
At the frequency f = f
Current:
±1.5% of the set value or ±0.002 × I
Voltage:
±1.5% of the set value or ±0.002 × U
Impedance:
±2.5% of the set value or ±0.05 Ω
Phase angle: ±2°
25 ms
2)
: 0.1...50
<8.5%
1MRS759142 C
Unit
Description
ohm
Second PE-loop
reactance, zone 4
ohm
PP-loop resistance, zone
4
ohm
PP-loop reactance, zone
4
ohm
Phase to earth reactance
in phase domain, zone 4
Direction of fault or load
zone 5
ohm
Direction resistance,
zone 5
ohm
Direction reactance,
zone 5
ohm
First PE-loop resistance,
zone 5
ohm
First PE-loop reactance,
zone 5
ohm
Second PE-loop
resistance, zone 5
ohm
Second PE-loop
reactance, zone 5
ohm
PP-loop resistance, zone
5
ohm
PP-loop reactance, zone
5
ohm
Phase to earth reactance
in phase domain, zone 5
n
n
Technical Manual