DSTPDIS has five flexible configurable impedance zones for protection (Z1...Z5).
Phase-to-earth distance protection is a basic earth-fault protection in solidly or low-
impedance earthed networks. Together with the phase preference logic, it also serves
as a selective protection function at cross-country faults in isolated or Petersen coil
compensated networks. In certain applications, system earthing is changed during
operation from high-impedance to low-impedance earthed system due to fault
location procedures. DSTPDIS can be used in such applications by setting System
grounding GFC to "From input" and by providing information about the type of
earthing through binary input SYS_EARTHING. Low (inactive) SYS_EARTHING
input indicates low-impedance earthing system.
DSTPDIS is suitable as a basic protection function against two- and three-phase faults
in various networks, regardless of the treatment of the neutral point. The independent
setting of the reach in the reactive and the resistive directions makes it possible to
create a fast and selective short circuit protection in many applications.

Signals

Table 848:
DSTPDIS Input signals
Name
Type
I3P
SIGNAL
I3P_PAR
SIGNAL
I3P_REF
SIGNAL
U3P
SIGNAL
URES
SIGNAL
BLOCK
BOOLEAN
SYS_EARTHING
BOOLEAN
TRIGG_REC
BOOLEAN
BLOCK_GFC
BOOLEAN
BLOCK_Z1
BOOLEAN
BLOCK_Z2
BOOLEAN
BLOCK_Z3
BOOLEAN
BLOCK_Z4
BOOLEAN
BLOCK_Z5
BOOLEAN
Table 849:
DSTPDIS Output signals
Name
Type
OPERATE_GFC
BOOLEAN
OPERATE_Z1
BOOLEAN
OPERATE_Z2
BOOLEAN
OPERATE_Z3
BOOLEAN
OPERATE_Z4
BOOLEAN
Table continues on next page
Protection functions
Default
Description
-
Three-phase currents
-
Three-phase currents
-
Three-phase currents
-
Three-phase voltages
-
Residual voltage
0=False
Block signal for activating the blocking mode
0=False
Network earthing method
0=False
External triggering for all recorded data
0=False
Block GFC operate
0=False
Block zone 1
0=False
Block zone 2
0=False
Block zone 3
0=False
Block zone 4
0=False
Block zone 5
Description
Time delayed operate signal, GFC
Time delayed operate signal, zone 1
Time delayed operate signal, zone 2
Time delayed operate signal, zone 3
Time delayed operate signal, zone 4