Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.2.1.10
Table 460:
EFLPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Time multiplier
Operate delay time
Operating curve type
Table 461:
EFLPTOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
REX640
Technical Manual
Table 458:
EFHPTOC Output signals
Name
OPERATE
START
Table 459:
EFIPTOC Output signals
Name
OPERATE
START

Settings

Unit
0.010...5.000
xIn
0.8...10.0
0.025...15.000
40...300000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Unit
1=Immediate
2=Def time reset
3=Inverse reset
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.005
0.010
0.1
1.0
0.005
1.000
10
40
15=IEC Def. Time
Step
Default
1=Immediate
Section 4
Protection functions
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
Selection of time delay curve type
Description
Selection of reset curve type
409