Section 4
Protection functions
4.2.1.8
4.2.1.9
408
Application
EFxPTOC is designed for protection and clearance of earth faults in distribution and
sub-transmission networks where the neutral point is isolated or earthed via a
resonance coil or through low resistance. It also applies to solidly earthed networks
and earth-fault protection of different equipment connected to the power systems,
such as shunt capacitor bank or shunt reactors and for backup earth-fault protection of
power transformers.
Many applications require several steps using different current start levels and time
delays. EFxPTOC consists of three different protection stages.
•
Low EFLPTOC
•
High EFHPTOC
•
Instantaneous EFIPTOC
EFLPTOC contains several types of time-delay characteristics. EFHPTOC and
EFIPTOC are used for fast clearance of serious earth faults.
Signals
Table 454:
EFLPTOC Input signals
Name
Type
IRES
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Table 455:
EFHPTOC Input signals
Name
Type
IRES
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Table 456:
EFIPTOC Input signals
Name
Type
IRES
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Table 457:
EFLPTOC Output signals
Name
Type
OPERATE
BOOLEAN
START
BOOLEAN
Default
Description
-
Residual current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Default
Description
-
Residual current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Default
Description
-
Residual current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Description
Operate
Start
1MRS759142 C
REX640
Technical Manual