Section 3
Basic functions
3.21.6.4
3.21.7
3.21.7.1
3.21.7.2
3.21.7.3
274
Table 277:
F_TRIG Output signals
Name
Q
Settings
The function does not have any parameters available in the LHMI or in PCM600.
Switching device status decoder CLOSE position
T_POS_CL, OPEN position T_POS_OP and OK status
T_POS_OK
Function block
GUID-E0C4183A-4A1F-4586-9831-62EA9C326CCB V1 EN
Figure 146:
Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is fed
to the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 278:
Cross reference between circuit breaker position and function block output
Circuit breaker position
Output of the function block
T_POS_CL
Intermediate '00'
FALSE
Close '01'
TRUE
Open '10'
FALSE
Faulty '11'
TRUE
Signals
Table 279:
T_POS_CL Input signals
Name
Type
POS
Double binary
Type
BOOLEAN
T_POS_OP
FALSE
FALSE
TRUE
TRUE
Default
0
1MRS759142 C
Description
Output signal
T_POS_OK
FALSE
TRUE
TRUE
FALSE
Description
Input signal
REX640
Technical Manual