Section 3
Basic functions
3.18.7
3.18.7.1
3.18.7.2
3.18.7.3
198
Received GOOSE measured value (phasor) information
GOOSERCV_CMV
Function block
GUID-10CDED37-2AF9-4601-8054-DF96DB0C3085 V1 EN
Figure 81:
Function block
Functionality
The received GOOSE measured value (phasor) information function
GOOSERCV_CMV is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.
Signals
Table 146:
GOOSERCV_CMV Input signals
Name
Type
MAG_IN
FLOAT32
ANG_IN
FLOAT32
Table 147:
GOOSERCV_CMV Output signals
Name
Type
MAG
FLOAT32
ANG
FLOAT32
VALID
BOOLEAN
Default
Description
0
Input signal
(amplitude)
0
Input signal (angle)
Description
Output signal (amplitude)
Output signal (angle)
Output signal
1MRS759142 C
REX640
Technical Manual