Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.3.2.8
622
GUID-FEBF3DEF-30BB-4A88-B8A6-BFED274DE6A8 V1 EN
Figure 345:
Alternative connection example of current transformers of Type 2
The CT secondary currents often differ from the rated current at the rated load of the
power transformer. The CT transforming ratios can be corrected on both sides of the
power transformer with the CT ratio Cor Wnd 1 and CT ratio Cor Wnd 2 settings.

Signals

Table 582:
TR2PTDF Input signals
Name
Type
I3P1
SIGNAL
I3P2
SIGNAL
BLOCK
BOOLEAN
BLK_OPR_LS
BOOLEAN
BLK_OPR_HS
BOOLEAN
TAP_POS
INT8
Default
Description
-
Three-phase currents 1
-
Three-phase currents 2
0=False
Block
0=False
Blocks operate outputs from biased stage
0=False
Blocks operate outputs from instantaneous stage
0
Tap position indication
1MRS759142 C
REX640
Technical Manual