Section 4
Protection functions
714
Connection of current transformers
The connections of the primary current transformers are designated as Type 1 and
Type 2.
If the positive directions of the winding 1 and winding 2 protection relay currents
are opposite, the CT connection type is of "Type 1". The connection examples of
"Type 1" are as shown in figures
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in figures
The default value of the CT connection type setting is "Type 1".
GUID-42CA1EAB-FC8C-4F99-912E-7264CFF2CAF3 V1 EN
Figure 393:
Connection of current transformer of Type 1, example 1
393
and 394.
395
and 396.
1MRS759142 C
REX640
Technical Manual