REX640
Technical Manual
Name
Type
IRES
SIGNAL
ALARM
BOOLEAN
WARNING
BOOLEAN

Monitored data

Table 245:
CMSWI Monitored data
Name
Type
SWITCH_POS
Enum

Generic up-down counter UDFCNT

Identification

Function description
Generic up-down counter

Function block

GUID-A99B42D1-CE1B-4120-BC35-F061E358D22F V1 EN
Figure 133:
Function block

Functionality

The Generic up-down counter function UDFCNT counts up or down for each positive
edge of the corresponding inputs. The counter value output can be reset to zero or
preset to some other value if required.
The function provides up-count and down-count status outputs, which specify the
relation of the counter value to a loaded preset value and to zero respectively.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
Description
Residual current
Alarm
Warning
Values (Range)
Unit
1=Source 1
2=Source 2
3=Source 3
4=Source 4
IEC 61850
IEC 60617
identification
identification
UDFCNT
UDCNT
Section 3
Basic functions
Description
Switch position
ANSI/IEEE C37.2
device number
UDCNT