Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.7.2.8
Table 860:
OOSRPSB Group settings (Basic)
Parameter
Oos operate mode
Forward reach
Reverse reach
Inner blinder R
Outer blinder R
Impedance angle
Swing time
Table 861:
OOSRPSB Group settings (Advanced)
Parameter
Zone 1 reach
Max number slips
Max Num slips Zn2
Max Num slips Zn3
Operate delay time
Operate dropout time
V dip time
Zone 2 enable
Zone 3 enable
Table 862:
OOSRPSB Non group settings (Basic)
Parameter
Operation
930

Settings

Values (Range)
Unit
1=Way in
2=Way out
3=Adaptive
0.00...6000.00
ohm
0.00...6000.00
ohm
1.00...6000.00
ohm
1.01...10000.00
ohm
10.0...90.0
deg
20...300000
ms
Values (Range)
Unit
1...100
%
1...10
1...20
1...20
20...60000
ms
20...60000
ms
500...5000
ms
1=Yes
0=No
1=Yes
0=No
Values (Range)
Unit
1=on
5=off
Step
Default
2=Way out
0.01
1000.00
0.01
100.00
0.01
150.00
0.01
400.00
0.1
90.0
10
500
Step
Default
1
70
1
1
1
1
1
1
10
300
10
100
10
2000
0=No
0=No
Step
Default
1=on
1MRS759142 C
Description
Operate mode for tripping when out of
step condition is detected
Forward reach of mho circle
Reverse reach of mho circle
Resistance value if inner blinder at R axis
Resistance value of outer blinder at R axis
Angle of mho circle and blinders with
respect to R axis
Time between blinders for swing to be
detected
Description
Percent of Mho forward reach indicating
the end of zone 1 and the beginning of
zone 2
Number of pole slips before operating
zone 1
Number of pole slips before operating
zone 2
Number of pole slips before operating
zone 3
Delay after OOS operate detected
Time operate output remains active
Maximum allowable time for voltage to dip
Enable zone 2 feature
Enable zone 3 feature
Description
Operation Off / On
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents