Section 8
Measurement functions
8.1.12.8
8.2
8.2.1
8.2.2
8.2.3
1332

Technical data

Table 1280:
PEMMXU Technical data
Characteristic
Operation accuracy
Suppression of harmonics
1) |PF| >0.5 which equals |cosφ| >0.5
2) |PF| <0.86 which equals |sinφ| >0.5
Disturbance recorder, common functionality RDRE
Identification
Function description
Disturbance recorder, common
functionality
Function block
GUID-2E79C7E8-EE7E-4AE6-8C1C-218AD2DB380F V1 EN
Figure 712:
Function block
Functionality
The protection relay is provided with a disturbance recorder featuring up to 24 analog
and 64 binary signal channels. The analog channels can be set to record either the
waveform or the trend of the currents and voltages measured and they can trigger the
recording function when the measured value falls below or exceeds the set values.
The binary signal channels can be set to start a recording either on the rising or the
falling edge of the binary signal or on both. By default, the binary channels are set to
record external or internal relay signals, for example, the start or trip signals of the
relay stages, or external blocking or control signals. Binary relay signals, such as
protection start and trip signals, or an external relay control signal via a binary input
Value
At all three currents in range 0.10...1.20 × I
At all three voltages in range 0.50...1.15 × U
At the frequency f
n
±1.5% for apparent power S
±1.5% for active power P and active energy
±1.5% for reactive power Q and reactive energy
±0.015 for power factor
DFT: -50 dB at f = n × f
IEC 61850
IEC 60617
identification
identification
RDRE
DR
1MRS759142 C
n
n
±1 Hz
1)
2)
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
DFR
REX640
Technical Manual