Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.2.6
REX640
Technical Manual
Protection relay
Insulating spindle
Disconnector
Fixed contact
contact
GUID-C7051A59-2C21-41A3-9E71-FC485F2157FC V1 EN
Figure 734:
Connection diagram for RIO600 control of a three-position
switchgear motor
When the RIO600 SCM module is selected as control mode, outputs
EXE_DCCLOSE, EXE_DCOPEN, EXE_ESCLOSE and
EXE_ESOPEN are connected in Application Configuration. When
direct motor control is selected as control mode, static outputs
H_UP_LEFT, H_UP_RIGHT, H_LO_LEFT and H_LO_RIGHT are
connected in Application Configuration.

Signals

Table 1320:
P3SXSWI Input signals
Name
Type
DCPOSOPEN
BOOLEAN
DCPOSCLOSE
BOOLEAN
ESPOSOPEN
BOOLEAN
ESPOSCLOSE
BOOLEAN
REED
BOOLEAN
Table continues on next page
Commands
Status
Earthing
Sliding part
contact
Default
Description
0=False
Signal for open position of disconnector
0=False
Signal for close position of disconnector
0=False
Signal for open position of earthing switch
0=False
Signal for close position of earthing switch
0=False
Signal for close position of reed contact
Section 9
Control functions
RIO600
Motor
Reed contact
1375