Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
10.1.8
Table 1441:
CHMHAI Non group settings (Basic)
Parameter
Values (Range)
Operation
Sliding interval
Table 1442:
CHMHAI Non group settings (Advanced)
Parameter
Values (Range)
Reference Cur Sel
Demand current
10.1.9
REX640
Technical Manual
Name
SMNH11_A
SMNH11_B
SMNH11_C

Settings

Unit
1=on
5=off
1=3 seconds
2=1 minute
3=5 minutes
Unit
0=fundamental
2=absolute
0.10...1.00
xIn
Monitored data
Table 1443:
CHMHAI Monitored data
Name
LMNTHD_A
LMNTHD_B
LMNTHD_C
LMNTDD_A
LMNTDD_B
LMNTDD_C
Table continues on next page
Power quality measurement functions
Type
Description
FLOAT32
Shorter mean value of 11th harmonic for Phase A
(%)
FLOAT32
Shorter mean value of 11th harmonic for Phase B
(%)
FLOAT32
Shorter mean value of 11th harmonic for Phase C
(%)
Step
Default
1=on
1=3 seconds
Step
Default
0=fundamental
0.01
1.00
Type
Values (Range)
FLOAT32
0.00...500.00
FLOAT32
0.00...500.00
FLOAT32
0.00...500.00
FLOAT32
0.00...500.00
FLOAT32
0.00...500.00
FLOAT32
0.00...500.00
Section 10
Description
Operation Off / On
Time interval for demand calculation
Description
Selection of reference current used with
individual harmonics
Reference current for harmonic demand
calculation
Unit
Description
%
Mean THD for phase A in
10 min non-sliding mean
in %
%
Mean THD for phase B in
10 min non-sliding mean
in %
%
Mean THD for phase C in
10 min non-sliding mean
in %
%
Mean TDD for phase A in
10 min non-sliding mean
in %
%
Mean TDD for phase B in
10 min non-sliding mean
in %
%
Mean TDD for phase C in
10 min non-sliding mean
in %
1609

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents