Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 5
Protection related functions
5.11.7
Table 1086:
RESCPSCH Non group settings (Basic)
Parameter
Operation
Scheme type
Carrier Min Dur
Coordination time
Table 1087:
RESCPSCH Non group settings (Advanced)
Parameter
Unblock mode
Loss of carrier time
5.11.8
5.11.9
1168

Settings

Values (Range)
Unit
1=on
5=off
1=None
2=Intertrip
3=Permissive
Underreach
4=Permissive
Overreach
5=Blocking
0...60000
ms
0...60000
ms
Values (Range)
Unit
1=Off
2=Permanent
3=Time window
0...60000
ms
Monitored data
Table 1088:
RESCPSCH Monitored data
Name
RESCPSCH
Technical data
Table 1089:
RESCPSCH Technical data
Characteristic
Operate time accuracy
Step
Default
1=on
3=Permissive
Underreach
1
100
1
35
Step
Default
1=Off
1
35
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
±1.0% of the set value or ±20 ms
1MRS759142 C
Description
Operation Off / On
Scheme type, mode of operation
Minimum duration of carrier send signal
Co-ordination timer for blocking scheme
Description
Unblock function mode for scheme type
Pickup security timer on loss of carrier
guard signal
Unit
Description
Status
Technical Manual