ABB RELION REX640 Technical Manual page 919

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Parameter
Values (Range)
Min Ris PP Rch Zn5
Max Ris PP Rch Zn5
PP operate delay Zn5
Op Mod Gnd loops Zn5
Gnd Op Dl mode Zn5
Load Comp zone 5
R0 zone 5
X0 zone 5
Factor K0 zone 5
Factor K0 angle Zn5
Min Ris Gnd Rch Zn5
Max Ris Gnd Rch Zn5
Gnd operate Dl Zn5
Table 851:
DSTPDIS Group settings (Advanced)
Parameter
Values (Range)
Gnd Op current 2 GFC
Stab slope 1 GFC
Stab slope 2 GFC
A Ph Stab value GFC
Dir mode EF GFC
Pol quantity GFC
Chr angle GFC
Max phase angle GFC
Min phase angle GFC
Table continues on next page
REX640
Technical Manual
Unit
0.00...100.00
ohm
0.00...100.00
ohm
20...60000
ms
0=False
1=True
0=False
1=True
0=False
1=True
0.00...3000.00
ohm
0.00...3000.00
ohm
0.0...4.0
-135...135
deg
0.00...500.00
ohm
0.00...500.00
ohm
20...60000
ms
Unit
0.10...10.00
xIn
0.00...0.30
0.00...1.00
1.00...10.00
xIn
1=Non-directional
2=Forward
3=Reverse
-1=Zro vol.OR cur.
2=Zero seq. cur.
3=Zero seq. volt.
4=Neg. seq. volt.
-179...180
deg
0...90
deg
0...90
deg
Step
Default
0.01
30.00
0.01
30.00
1
20
0=False
1=True
1=True
0.01
160.00
0.01
160.00
0.1
1.0
1
0
0.01
100.00
0.01
100.00
1
20
Step
Default
0.01
1.00
0.01
0.10
0.01
1.00
0.01
2.00
1=Non-directional
3=Zero seq. volt.
1
75
1
80
1
80
Section 4
Protection functions
Description
Minimum resistive reach of PP/3P-loops,
zone 5
Maximum resistive reach of PP/3P-loops,
zone 5
Time delay to operate of PP/3P-loops,
zone 5
Enable PE-loop measurement, zone 5
Enable operate timer for PE-loops, zone 5
Enable load compensation for PE-loops,
zone 5
Zero sequence resistive reach, zone 5
Zero sequence reactive reach, zone 5
Residual compensation factor magnitude,
zone 5
Residual compensation factor angle,
zone 5
Minimum resistive reach of PE-loops,
zone 5
Maximum resistive reach of PE-loops,
zone 5
Time delay to operate of PE-loops, zone 5
Description
Res. curr. start value for slope 2, EF-
detection function
Slope 1 for res. curr. stabilization, EF-
detection function
Slope 2 for res. current stabilization, EF-
detection function
Phase current start value for slope 2, EF-
detection function
Directional mode, earth-fault directional
function
Polarization method, earth-fault
directional function
Characteristic angle, earth-fault
directional function
Right hand side angle, earth-fault
directional function
Left hand side angle, earth-fault
directional function
913