1MRS759142 C
REX640
Technical Manual
The Operation mode setting in the "IIt, CB" mode enables the function to calculate the
value of the thermal stress when a start-up is monitored in addition to the CB_CLOSED
input.
In the "IIt & stall" mode, the function calculates the thermal stress of the motor during
the start-up condition. The start-up condition is detected by monitoring the TRMS
currents.
In the "IIt & stall, CB" mode, the function calculates the thermal stress of the motor
during the start-up condition but the start-up condition is detected by monitoring the
TRMS current as well as the circuit breaker status.
In both the "IIt & stall" and "IIt & stall, CB" mode, the function also checks for motor
stalling by monitoring the speed switch.
When the measured current value is used for start-up supervision in the "IIt" and "IIt
& stall" modes, the module initially recognizes the de-energized condition of the
motor when the values of all three phase currents are less than Motor standstill A for
longer than 100 milliseconds. If any of the phase currents of the de-energized
condition rises to a value equal to or greater than Motor standstill A, the MOT_START
output signal is activated indicating that the motor start-up is in progress. The
MOT_START output remains active until the values of all three phase currents drop
below 90 percent of the set value of Start detection A and remain below that level for
a time of Str over delay time, that is, until the start-up situation is over.
GUID-15B19852-C3E8-4E73-8E0F-E208AA22B4B2 V1 EN
Figure 539:
Functionality of start-up supervision in the "IIt and IIt&stall" mode
In case of the "IIt, CB" or "IIt & stall, CB" modes, the function initially recognizes the
de-energized condition of the motor when the value of all three phase currents is below
the value of the Motor standstill A setting for 100 milliseconds. The beginning of the
motor start-up is recognized when CB is closed, that is, when the CB_CLOSED input
is activated and at least one phase current value exceeds the Motor standstill A setting.
Section 4
Protection functions
995