ABB RELION REX640 Technical Manual page 767

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
GUID-2E232A83-5363-4153-8085-34BC36BF0F28 V1 EN
Figure 419:
MNSPTOC Inverse Curve A
If the negative sequence current drops below the Start value setting, the reset time is
defined as:
b
t s
a
[ ]
= ⋅
100
GUID-1A0607E9-C631-4AC9-A195-7D0E13AD9C52 V1 EN
t[s] Reset time in seconds
Cooling time
a
set
b
percentage of start time elapse (START_DUR)
Section 4
Protection functions
(Equation 192)
761