Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
6.8.8
Table 1182:
MSVPR Non group settings (Basic)
Parameter
Values (Range)
Operation
Start value
Operate delay time
Voltage selection
Num of phases
Phase supervision
Table 1183:
MSVPR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
6.8.9
REX640
Technical Manual
Table 1181:
MSVPR Output signals
Name
U_LOW

Settings

Unit
1=on
5=off
0.05...1.20
xUn
100...300000
ms
1=phase-to-earth
2=phase-to-phase
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=A or AB
2=B or BC
4=C or CA
7=A&B&C or
AB&BC&CA
Unit
0...60000
ms
Monitored data
Table 1184:
MSVPR Monitored data
Name
U_AMPL_A
U_AMPL_B
U_AMPL_C
U_AMPL_AB
Table continues on next page
Type
Description
BOOLEAN
Low remanent voltage
Step
Default
1=on
0.01
0.25
100
100
2=phase-to-phase
3=3 out of 3
7=A&B&C or
AB&BC&CA
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...5.00
FLOAT32
0.00...5.00
FLOAT32
0.00...5.00
FLOAT32
0.00...5.00
Section 6
Supervision functions
Description
Operation Off / On
Start value
Operate delay time
Parameter to select phase or phase-to-
phase voltages
Number of phases required for voltage
supervision
Monitored voltage phase
Description
Reset delay time
Unit
Description
xUn
Remanent voltage of
phase A
xUn
Remanent voltage of
phase B
xUn
Remanent voltage of
phase C
xUn
Remanent voltage of
phase to phase AB
1245