Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.9.7
REX640
Technical Manual
the time set with the Reclaim time parameter. Furthermore, if the Fourth delay in
SOTF parameter is "1", the Str _ delay shot 4 parameter delays are also activated.
Example 1
The protection operation time is 0.5 seconds, the Fourth delay in SOTF parameter is
set to "1" and the Str 2 delay shot 4 parameter is 0.05 seconds. The protection start
signal is connected to the DEL_INIT_2 input.
If the protection starts after the circuit breaker closes, the fast trip follows after the set
0.05 seconds. The total trip time is the protection start delay + 0.05 seconds + the time
it takes to open the circuit breaker.

Signals

Table 1403:
DARREC Input signals
Name
Type
INIT_1
BOOLEAN
INIT_2
BOOLEAN
INIT_3
BOOLEAN
INIT_4
BOOLEAN
INIT_5
BOOLEAN
INIT_6
BOOLEAN
DEL_INIT_2
BOOLEAN
DEL_INIT_3
BOOLEAN
DEL_INIT_4
BOOLEAN
BLK_RECL_T
BOOLEAN
BLK_RCLM_T
BOOLEAN
BLK_THERM
BOOLEAN
CB_POS
BOOLEAN
CB_READY
BOOLEAN
INC_SHOTP
BOOLEAN
INHIBIT_RECL
BOOLEAN
RECL_ON
BOOLEAN
SYNC
BOOLEAN
Table 1404:
DARREC Output signals
Name
Type
OPEN_CB
BOOLEAN
CLOSE_CB
BOOLEAN
CMD_WAIT
BOOLEAN
Table continues on next page
Default
Description
0=False
AR initialization / blocking signal 1
0=False
AR initialization / blocking signal 2
0=False
AR initialization / blocking signal 3
0=False
AR initialization / blocking signal 4
0=False
AR initialization / blocking signal 5
0=False
AR initialization / blocking signal 6
0=False
Delayed AR initialization / blocking signal 2
0=False
Delayed AR initialization / blocking signal 3
0=False
Delayed AR initialization / blocking signal 4
0=False
Blocks and resets reclose time
0=False
Blocks and resets reclaim time
0=False
Blocks and holds the reclose shot from the thermal
overload
0=False
Circuit breaker position input
1=True
Circuit breaker status signal
0=False
A zone sequence coordination signal
0=False
Interrupts and inhibits reclosing sequence
0=False
Level sensitive signal for allowing (high) / not
allowing (low) reclosing
0=False
Synchronizing check fulfilled
Description
Open command for circuit breaker
Close (reclose) command for circuit breaker
Wait for master command
Section 9
Control functions
1533