1MRS759142 C
5.9.4
5.9.5
REX640
Technical Manual
DSTPLAL can be controlled either by the autorecloser (zone extension logic) or by
monitoring the loss of load currents (the loss of load logic). Both operation modes are
enabled independently.

Analog channel configuration

DSTPLAL has one analog group input which must be properly configured.
Table 1068:
Analog inputs
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
The operation of DSTPLAL can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
EX_ACC
AR_READY
NONDIR_ST
I3P
LOSSLOAD_ACC
CB_CL_CMD
BLOCK
GUID-3E377773-BBF5-4609-9696-006C44E936F2 V1 EN
Figure 612:
Functional module diagram
Zone extension logic
Zone extension logic is enabled with Operation mode = "Zone extension".
Protection related functions
Description
Three-phase currents
Zone
extension
logic
I_A
I_B
I_C
Loss of
OPR_LOSSLOAD
load logic
Section 5
OPR_Z_EXTN
1133