The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself.

Analog channel configuration

HREFPDIF has one analog group input which must be properly configured.
Table 614:
Analog inputs
Input
IRES
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of HREFPDIF can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
Level
Io
IRES
detector
Blocking
BLOCK
logic
GUID-B5C6CFD0-1190-4CFD-AF78-655874E52C12 V1 EN
Figure 373:
Functional module diagram
Level detector
The level detector compares the differential neutral current IDo to the set value of the
Operate value setting. If the differential neutral current exceeds the Operate value
setting, the level detector sends an enable signal to the timer module to start the
definite timer.
Protection functions
Description
Residual current (measured)
Timer
OPERATE
t
START
Section 4
673