Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of HAEFPTOC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
Harmonics
Io
IRES
calculation
I_REF_RES
BLOCK
GUID-792AC03A-0E40-4406-B217-99AE844B0340 V1 EN
Figure 268:
Functional module diagram
Harmonics calculation
This module feeds the measured residual current to the high-pass filter, where the
frequency range is limited to start from two times the fundamental frequency of the
network (for example, in a 50 Hz network the cutoff frequency is 100 Hz), that is,
summing the harmonic components of the network from the second harmonic. The
output of the filter, later referred to as the harmonics current, is fed to the Level
detector and Current comparison modules.
The harmonics current I_HARM_RES is available in the monitored data view. The
value is also sent over horizontal communication to the other protection relays on the
parallel feeders configured in the protection scheme.
Timer
Level
detector
t
t
Current
comparison
Blocking
logic
Section 4
Protection functions
START
OPERATE
489