Control Mode - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 59:
Station authority level "L,S,S+R,L+S,L+S+R" using R/L button
L/R Control
R/L button
CTRL.LLN0.LocSta
Local
FALSE
Remote
FALSE
Remote
TRUE
Local +
FALSE
Remote
Local +
TRUE
Remote
Off
FALSE
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
Table 60:
Station authority level "L,S,S+R,L+S,L+S+R" using CONTROL function block
L/R Control
Control FB input CTRL.LLN0.LocSta
CTRL_OFF
FALSE
CTRL_LOC
FALSE
CTRL_STA
FALSE
TRUE
4)
CTRL_REM
CTRL_REM
FALSE
CTRL_ALL
FALSE
TRUE
4)
CTRL_ALL
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.8.8
REX640
Technical Manual
L/R Control status
CTRL.LLN0.MltLev
1)
FALSE
TRUE
FALSE
TRUE
TRUE
FALSE
L/R Control status
CTRL.LLN0.MltLev
1)
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE

Control mode

The function has two outputs BEH_TST and BEH_BLK which are activated in test
mode according to
Table
Table 61:
Control mode
Control mode
On
Blocked
Off
L/R state
CTRL.LLN0.LocKeyHMI
1
7
3
6
5
0
L/R state
CTRL.LLN0.LocKeyHMI
0
1
3
3
7
6
5
61.
Description
Normal operation
Control function commands
blocked
Control functions disabled
Section 3
Basic functions
Control access
Local user
IEC 61850
2)
client
x
x
x
x
x
Control access
Local user
IEC 61850
2)
client
x
x
x
x
x
Control BEH_BLK
FALSE
TRUE
FALSE
IEC 61850
3)
client
x
x
x
x
IEC 61850
3)
client
x
x
x
x
x
129