Section 3
Basic functions
3.17.2.4
Table 125:
Non group settings
Parameter
Primary current
Secondary current
Rated current
Amplitude Corr
Reverse polarity
Angle correction
Frequency adaptivity
3.17.2.5
186
The SMV Max Delay setting defines how long the receiver waits for the SMV frames
before activating the ALARM output. This setting can be accessed via Configuration/
System. Waiting for the SMV frames also delays the local measurements of the
receiver to keep them correctly time aligned. The SMV Max Delay values include
sampling, processing and network delay.
Frequency adaptive measurements for residual current can be activated with the
setting Frequency adaptivity. Two selections are provided.
Table 124:
Frequency adaptivity setting for residual current measurement
Setting value
Disable
Enable
RESTCTR setting Frequency adaptivity is visible only if system
setting Configuration/System/Frequency adaptivity is set to
"Enable".

Settings

Values (Range)
Unit
1.0...6000.0
A
1=0.2A
2=1A
3=5A
1.0...6000.0
A
0.9000...1.1000
0=False
1=True
-20.0000...20.0000
deg
0=Disable
1=Enable

Monitored data

Monitored data is available in three locations.
Monitoring/I/O status/Analog inputs
Monitoring/IED status/SMV traffic
Monitoring/IED status/SMV accuracy
Description
Frequency adaptive measurements are disabled
for this UTVTR. Measurements are fixed to
nominal frequency defined with Configuration/
System/Rated frequency.
Frequency adaptive measurements are enabled.
In this case, the estimated network frequency is
defined by another preprocessing block.
Step
Default
0.1
100.0
2=1A
0.1
100.0
0.0001
1.0000
0=False
0.0001
0.0000
0=Disable
1MRS759142 C
Description
Primary current
Secondary current
Network rated current (Ir)
Amplitude correction
Reverse the polarity of the residual CT
Angle correction factor
Frequency adaptivity selection
Technical Manual