1MRS759142 C
4.7.1.4
REX640
Technical Manual
50
SIR 50
SIR 30
45
SIR 10
SIR 5
SIR 0.5
40
SIR 0.2
35
30
25
20
15
0
10
20
GUID-B0D18BB9-21AB-4AEB-9943-D56773D09E64 V1 EN
Figure 465:
Average operate time of DSTPDIS according to IEC 60255-121
network models Short line and Long line (50 Hz)
SIR curves are plotted from the data which includes variation of fault location (0...
100% of zone reach, 5% step), fault type (LN, LL, LLN, LLL) and fault inception
angle (0, 30, 60, 90 degrees). Each combination has been repeated ten times giving the
total number of 26880 shots. The operate times include the delay of relay output
contacts. The SIR curves presented in
outputs (SPOs) and with Zone timer mode = "common".

Analog channel configuration

DSTPDIS has five analog group inputs which must be properly configured.
Average Operate time
30
40
50
Fault location [% of zone reach]
Figure 465
were obtained using the static power
Section 4
Protection functions
60
70
80
90
100
861