Section 4
Protection functions
4.8.1.7
4.8.1.8
Table 892:
DUPPDPR Group settings (Basic)
Parameter
Start value
Operate delay time
Table 893:
DUPPDPR Non group settings (Basic)
Parameter
Operation
958
If the measuring errors are not compensated for, the underpower
setting should not be lower than the sum of the current-measuring and
voltage-measuring errors.
For example, if the error of the current-measuring device is 2% and
that of the voltage-measuring device is 1%, the minimum setting is (2
+ 1)% = 3%.

Signals

Table 890:
DUPPDPR Input signals
Name
I3P
U3P
BLOCK
DISABLE
Table 891:
DUPPDPR Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
0.01...2.00
xSn
40...300000
ms
Values (Range)
Unit
1=on
5=off
Type
Default
Description
SIGNAL
-
Three-phase currents
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Signal to block the function during generator
startup
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.10
10
40
Step
Default
1=on
1MRS759142 C
Description
Start value
Operate delay time
Description
Operation On/Off
Technical Manual