Section 6
Supervision functions
6.1.5
1198
TCS
TCS_STATE
status
BLOCK
GUID-147DACFF-C3A6-4874-A08F-6387EF323097 V2 EN
Figure 649:
Functional module diagram
TCS status
This module receives the trip circuit status from the hardware. A detected failure in the
trip circuit activates the timer.
Timer
Once activated, the timer runs until the set value of Operate delay time has elapsed.
The time characteristic is according to DT. When the operation timer has reached the
maximum time value, the ALARM output is activated. If a drop-off situation occurs
during the operate time up counting, the fixed 0.5 s reset timer is activated. After that
time, the operation timer is reset.
The BLOCK input can be controlled with a binary input, a horizontal communication
input or an internal signal of the relay program. The activation of the BLOCK input
prevents the ALARM output to be activated.

Application

TCSSCBR detects faults in the electrical control circuit of the circuit breaker. The
function can supervise both open and closed coil circuits. This supervision is
necessary to find out the vitality of the control circuits continuously.
Figure 650
shows an application of the trip circuit supervision function use. Example
of both mechanical (on the left) and static (on the right) outputs TCS connections are
shown.
The mechanical outputs (PODPx) are used in both AC or DC circuits,
and polarity is insignificant. The static outputs (SPOx) can be used in
DC only and polarity must be correct.
The best solution is to connect an external R
breaker internal contact as shown with the dashed line. This way, although the circuit
breaker auxiliary contact is open, TCS can see the trip circuit through R
resistor should have such a resistance that the current through the circuit breaker coil
remains small, that is, it does not harm or overload the circuit breaker's trip coil if the
trip is latched/locked-out.
Timer
t
ALARM
shunt resistor in parallel with the circuit
ext
1MRS759142 C
. The R
ext
ext
REX640
Technical Manual