Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 710:
PHPTOV Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
Type of time reset
Table 711:
PHPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
Num of start phases
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Voltage selection
Table 712:
PHPTOV Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Curve Sat Relative
Relative hysteresis
4.5.1.10
REX640
Technical Manual
Unit
1=Immediate
2=Def time reset
1=Freeze Op timer
2=Decrease Op
timer
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
0.005...200.000
0.50...100.00
0.0...1.0
0.000...60.000
0.000...3.000
1=phase-to-earth
2=phase-to-phase
Unit
40...60000
ms
0...60000
ms
0.0...10.0
1.0...5.0
%

Monitored data

Table 713:
PHPTOV Monitored data
Name
START_DUR
PHPTOV
Step
Default
1=Immediate
1=Freeze Op timer
Step
Default
1=on
1=1 out of 3
1
1.000
1
1.00
1
0.0
1
0.000
1
1.000
2=phase-to-phase
Step
Default
1
40
1
20
0.1
0.0
0.1
4.0
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Selection of reset curve type
Selection of time reset
Description
Operation Off / On
Number of phases required for operate
activation
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Parameter to select phase or phase-to-
phase voltages
Description
Minimum operate time for IDMT curves
Reset delay time
Tuning parameter to avoid curve
discontinuities
Relative hysteresis for operation
Unit
Description
%
Ratio of start time /
operate time
Status
773