4.2.4.9
Table 515:
EFPADM Group settings (Basic)
Parameter
Values (Range)
Voltage start value
Directional mode
Operation mode
Operate delay time
Circle radius
Circle conductance
Circle susceptance
Conductance forward
Conductance reverse
Susceptance forward
Susceptance reverse
Table 516:
EFPADM Group settings (Advanced)
Parameter
Values (Range)
Conductance tilt Ang
Susceptance tilt Ang
Table 517:
EFPADM Non group settings (Basic)
Parameter
Values (Range)
Operation
REX640
Technical Manual

Settings

Unit
0.01...2.00
xUn
1=Non-directional
2=Forward
3=Reverse
1=Yo
2=Go
3=Bo
4=Yo, Go
5=Yo, Bo
6=Go, Bo
7=Yo, Go, Bo
60...300000
ms
0.05...500.00
mS
-500.00...500.00
mS
-500.00...500.00
mS
-500.00...500.00
mS
-500.00...500.00
mS
-500.00...500.00
mS
-500.00...500.00
mS
Unit
-30...30
deg
-30...30
deg
Unit
1=on
5=off
Step
Default
0.01
0.15
2=Forward
1=Yo
10
60
0.01
1.00
0.01
0.00
0.01
0.00
0.01
1.00
0.01
-1.00
0.01
1.00
0.01
-1.00
Step
Default
1
0
1
0
Step
Default
1=on
Section 4
Protection functions
Description
Voltage start value
Directional mode
Operation criteria
Operate delay time
Admittance circle radius
Admittance circle midpoint, conductance
Admittance circle midpoint, susceptance
Conductance threshold in forward
direction
Conductance threshold in reverse
direction
Susceptance threshold in forward
direction
Susceptance threshold in reverse
direction
Description
Tilt angle of conductance boundary line
Tilt angle of susceptance boundary line
Description
Operation Off / On
479