Section 3
Basic functions
Parameter
Description
Operation mode
Pulse length
Description
Operation mode
Pulse length
Description
3.20.14
3.20.14.1
3.20.14.2
3.20.14.3
244
Values (Range)
Unit
0=Pulsed
1=Toggle/
Persistent
-1=Off
10...3600000
ms
0=Pulsed
1=Toggle/
Persistent
-1=Off
10...3600000
ms
Pulse counter for energy measurement PCGAPC
Identification
Function description
Pulse counter for energy measurement
Function block
GUID-8814F937-E64C-45C7-ACEE-6A65EA3EBEE5 V1 EN
Figure 124:
Function block
Functionality
The pulse counter for energy measurement function PCGAPC counts externally
generated binary pulses, for example, pulses coming from an external energy meter,
for the calculation of energy consumption values. The pulses are captured by the
binary input module and read by PCGAPC. The number of pulses in the counter is then
reported via the station bus to the automation system or read via the station monitoring
system as a service value. The scaled value is also available over IEC 61850
communication.
Step
Default
SPCGAPC1
Output 14
-1=Off
10
1000
SPCGAPC1
Output 15
-1=Off
10
1000
SPCGAPC1
Output 16
IEC 61850
identification
PCGAPC
1MRS759142 C
Description
Generic control point description
Operation mode for generic control point
Pulse length for pulsed operation mode
Generic control point description
Operation mode for generic control point
Pulse length for pulsed operation mode
Generic control point description
IEC 60617
ANSI/IEEE C37.2
identification
device number
PCGAPC
PCGAPC
Technical Manual
REX640