1MRS759142 C
REX640
Technical Manual
Fault indication
SO-relay(s),slot C
SO-relay(s),slot E
SO-relay(s),slot B
SO-relay(s),slot D
SO-relay(s),slot G
PO-relay(s),slot C
PO-relay(s),slot E
PO-relay(s),slot B
PO-relay(s),slot D
PO-relay(s),slot G
Conf.error,slot C
Conf.error,slot E
Conf.error,slot A2
Conf.error,slot B
Conf.error,slot D
Conf.error,slot F
Conf.error,slot G
Conf.error,slot A1
Card error,slot C
Table continues on next page
Fault code
-10
-11
-13
-14
-16
-20
-21
-23
-24
-26
-30
-31
-32
-33
-34
-35
-36
-37
-40
Section 3
Basic functions
Additional information
Faulty Signal Output relay(s) in
module located in slot C
Faulty Signal Output relay(s) in
module located in slot E
Faulty Signal Output relay(s) in
module located in slot B
Faulty Signal Output relay(s) in
module located in slot D
Faulty Signal Output relay(s) in
module located in slot G
Faulty Power Output relay(s) in
module located in slot C
Faulty Power Output relay(s) in
module located in slot E
Faulty Power Output relay(s) in
module located in slot B
Faulty Power Output relay(s) in
module located in slot D
Faulty Power Output relay(s) in
module located in slot G
Module in slot C is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot E is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot A2 is wrong type,
is missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot B is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot D is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot F is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot G is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot A1 is wrong type,
is missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot C is faulty.
101