Minimum Pulse Timer Second Resolution, Two Channels Tpsgapc - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 184:
TPGAPC Non group settings (Basic)
Parameter
Values (Range)
Pulse time
3.20.1.2
REX640
Technical Manual
timers are used for setting the minimum pulse length for example, the signal outputs.
Once the input is activated, the output is set for a specific duration using the Pulse time
setting. Both timers use the same setting parameter.
GUID-B744FA36-0C8F-42B5-8237-503FE49C80C2 V1 EN
Figure 98:
A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is
longer than Pulse time setting
Signals
Table 182:
TPGAPC Input signals
Name
IN1
IN2
Table 183:
TPGAPC Output signals
Name
OUT1
OUT2
Settings
Unit
0...60000
ms

Minimum pulse timer second resolution, two channels TPSGAPC

Identification
Function description
Minimum pulse timer second resolution,
two channels
Type
Default
Description
BOOLEAN
0=False
Input 1
BOOLEAN
0=False
Input 2
Type
Description
BOOLEAN
Output 1 status
BOOLEAN
Output 2 status
Step
Default
1
0
IEC 61850
identification
TPSGAPC
Section 3
Basic functions
Description
Minimum pulse time
IEC 60617
ANSI/IEEE C37.2
identification
device number
TPS
62TPS
213