Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
3.17.1.4
REX640
Technical Manual
Table 119:
Frequency adaptivity setting for three-phase current measurement
Setting value
Disable
Enable
Backup frequency source
All three phases must be always connected.
ILTCTR setting Frequency adaptivity is visible only if the system
setting Configuration/System/Frequency adaptivity is set to
"Enable".

Signals

Table 120:
ILTCTR Input signals
Name
Type
IL1
SIGNAL
IL2
SIGNAL
IL3
SIGNAL
Table 121:
ILTCTR Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN
I3P
SIGNAL
IRES_CLC
SIGNAL
IRES_CLC_DR
SIGNAL
IL1_DR
SIGNAL
IL2_DR
SIGNAL
Table continues on next page
Description
Frequency adaptive measurements are disabled
for this ILTCTR. Measurements are fixed to
nominal frequency defined with Configuration/
System/Rated frequency.
Frequency adaptive measurements are enabled.
In this case, the estimated network frequency is
defined by another preprocessing block.
Frequency adaptive measurements are enabled.
If the main frequency source cannot determine the
network frequency, the currents of the
preprocessing block determine the network
frequency.
Default
Description
-
Analog input
-
Analog input
-
Analog input
Description
Alarm
Warning
Three-phase currents
Residual current, calculated
Residual current, calculated, for disturbance
recorder
Phase current IL1 for disturbance recorder
Phase current IL2 for disturbance recorder
Section 3
Basic functions
183