1MRS759142 C
Table 466:
EFHPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Table 467:
EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Table 468:
EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Operate delay time
Table 469:
EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 470:
EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
REX640
Technical Manual
Unit
1=on
5=off
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
Unit
1.00...40.00
xIn
0.8...10.0
20...300000
ms
Unit
1=on
5=off
Unit
0...60000
ms
Step
Default
1=on
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Step
Default
1
20
1
20
2=DFT
Step
Default
0.01
1.00
0.1
1.0
10
20
Step
Default
1=on
Step
Default
1
20
Section 4
Protection functions
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Description
Start value
Multiplier for scaling the start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
411