ABB RELION REX640 Technical Manual page 595

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 576:
LNPLDF Non group settings (Basic)
Parameter
Values (Range)
Operation
Winding selection
Winding 1 type
Winding 2 type
Clock number
CT ratio correction
CT connection type
Zro A elimination
Restraint mode
Table 577:
LNPLDF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
Minimum operate time
REX640
Technical Manual
Unit
1=on
4=test/blocked
5=off
1=Not in use
2=Winding 1
3=Winding 2
1=Y
2=YN
3=D
4=Z
5=ZN
1=y
2=yn
3=d
4=z
5=zn
0=Clk Num 0
1=Clk Num 1
2=Clk Num 2
4=Clk Num 4
5=Clk Num 5
6=Clk Num 6
7=Clk Num 7
8=Clk Num 8
10=Clk Num 10
11=Clk Num 11
0.200...5.000
1=Type 1
2=Type 2
1=Not eliminated
2=Winding 1
3=Winding 2
4=Winding 1 and 2
1=None
2=Harmonic2
Unit
0...60000
ms
45...60000
ms
Step
Default
1=on
1=Not in use
1=Y
1=y
0=Clk Num 0
0.001
1.000
1=Type 1
1=Not eliminated
1=None
Step
Default
1
0
1
45
Section 4
Protection functions
Description
Operation mode of the function
IED location respect to transformer, HV
(Winding 1) side or LV (Winding 2) side
Connection of the HV side windings
Connection of the LV side windings
Setting the phase shift between HV and
LV with clock number for connection
group compensation (e.g. Dyn11 -> 11)
Local phase current transformer ratio
correction
CT connection type. Determined by the
directions of the connected current
transformers.
Elimination of the zero-sequence current
Selects what restraint modes are in use
Description
Reset delay time for stabilized stage
Minimum operate time for stabilized stage
IDMT curves
589