ABB RELION REX640 Technical Manual page 1003

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
GUID-22BDB73F-F0A3-44F6-9AD4-F35CCC5D0C62 V1 EN
GUID-0C960A25-8106-4FE0-B5AF-D15A478C8969 V1 EN
Figure 540:
Functionality of start-up supervision in the "IIt, CB" mode and the "IIt
and stall, CB" mode
The Str over delay time setting has different purposes in different modes of operation.
In the "IIt" or "IIt & stall" modes, the aim of this setting is to check for the
completion of the motor start-up period. The purpose of this time delay setting is
to allow for short interruptions in the current without changing the state of the
MOT_START output. In this mode of operation, the value of the setting is in the
range of around 100 milliseconds.
In the "IIt, CB" or "IIt & stall, CB" modes, the purpose of this setting is to check
for the life of the protection scheme after the CB_CLOSED input has been
activated. Based on the values of the phase currents, the completion of the start-
up period cannot be judged. So in this mode of operation, the value of the time
delay setting can even be as high as within the range of seconds, for example
around 30 seconds.
Section 4
Protection functions
997

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents