Signals; Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.3.8.9
4.3.8.10
Table 655:
MHZPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
Minimum operate time
Table 656:
MHZPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 657:
MHZPDIF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
REX640
Technical Manual
The sensitivity of the protection can be re-calculated taking into account the leakage
current through the varistor as per
I
1000 0 020
.
(
=
prim
GUID-59E56BFE-FD64-493B-96F0-0F412D1B4F62 V1 EN

Signals

Table 653:
MHZPDIF Input signals
Name
I3P
BLOCK
Table 654:
MHZPDIF Output signals
Name
OPERATE
START

Settings

Unit
0.5...50.0
%In
20...300000
ms
Unit
1=on
5=off
Unit
0...60000
ms
Equation
A
2 0 0085
.
A
0 002
.
A
+ ⋅
+
Type
Default
Description
SIGNAL
-
BOOLEAN
0=False
Type
Description
BOOLEAN
BOOLEAN
Step
Default
0.1
0.5
10
20
Step
Default
1=on
Step
Default
1
0
Protection functions
170.
39
A
)
Three-phase currents
Block signal for activating the blocking mode
Operate
Start
Description
Operate value, percentage of the nominal
current
Minimum operate time
Description
Operation Off / On
Description
Reset delay time
Section 4
(Equation 188)
733