Section 5
Protection related functions
5.5.3
5.5.4
1088

Functionality

The binary signal transfer function BSTGAPC is used for transferring binary signals
between the local and remote end line differential protection relays. The function
includes eight binary signals that are transferred in the protection communication
telegram and can be freely configured and used for any purpose in the line differential
application.
BSTGAPC transfers binary data continuously over the protection communication
channel between the terminals. Each of the eight signals are bidirectional and the
binary data sent locally is available remotely as a received signal.
BSTGAPC includes a minimum pulse time functionality for the received binary
signals. Each received signal has its own minimum pulse time setting parameter.
BSTGAPC includes two alarm output signals. The SEND_SIG_A output signal is
updated according to the status of the sent binary signals. The RECV_SIG_A output
signal is updated according to the status of the received binary signals. Each signal can
be separately included or excluded from the alarm logic with a setting parameter.
Operation principle
The Signal 1...8 mode setting can be used for changing the operation of the
bidirectional signal channel. The signal channel can be disabled by setting the
corresponding parameter value to "Not in use". When the signal channel is disabled
locally or remotely, the corresponding RECV_SIG_1...8 signal status is always
false on both ends.
GUID-B701E942-A266-49FA-B925-5AF0DDB98BF6 V1 EN
Figure 590:
Functional module diagram
1MRS759142 C