Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.1.5
768
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of PHPTOV can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
U_A_AB
U_B_BC
U3P
U_C_CA
BLOCK
GUID-11C63ED6-BA36-431F-8D8C-C80E9771B332 V1 EN
Figure 422:
Functional module diagram
Level detector
The fundamental frequency component of the measured three-phase voltages are
compared phase-wise to the set value of the Start value setting. If the measured value
is higher than the set value of the Start value setting, the level detector enables the
phase selection logic module. The Relative hysteresis setting can be used for
preventing unnecessary oscillations if the input signal slightly differs from the Start
value setting. After leaving the hysteresis area, the start condition has to be fulfilled
again and it is not sufficient for the signal to only return to the hysteresis area.
The Voltage selection setting is used for selecting phase-to-earth or phase-to-phase
voltages for protection.
For the voltage IDMT operation mode, the used IDMT curve equations contain
discontinuity characteristics. The Curve Sat relative setting is used for preventing
undesired operation.
For a more detailed description of the IDMT curves and the use of the
Curve Sat Relative setting, see the
overvoltage protection
Phase
Level
selection
detector
logic
Blocking
logic
IDMT curve saturation of
section in this manual.
1MRS759142 C
OPERATE
OPR_A
Timer
OPR_B
t
OPR_C
START
t
ST_A
ST_B
ST_C
REX640
Technical Manual