Section 4
Protection functions
4.11
4.11.1
4.11.2
4.11.3
4.11.4
1006

Multipurpose protection MAPGAPC

Identification
Function description
Multipurpose protection
Function block
GUID-B95AC385-E6C0-4D5D-93CF-C02E9BD76AAA V1 EN
Figure 544:
Function block
Functionality
The multipurpose protection function MAPGAPC is used as a general protection with
many possible application areas as it has flexible measuring and setting facilities. The
function can be used as an under- or overprotection with a settable absolute hysteresis
limit. The function operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
The operation of MAPGAPC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
AI_VALUE
Level
detector
ENA_ADD
Blocking
BLOCK
logic
GUID-44403415-6C48-4F37-A280-F8C14EA0DBF5 V1 EN
Figure 545:
Functional module diagram
IEC 61850
IEC 60617
identification
identification
MAPGAPC
MAP
Timer
OPERATE
t
START
1MRS759142 C
ANSI/IEEE C37.2
device number
MAP
REX640
Technical Manual