ABB RELION REX640 Technical Manual page 943

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
Q (Reactive power) p.u.
Motor
A
0.9
0.6
Over-Excitation
0.0
Under-Excitation
0.3
E
0.5
D
GUID-BFBC3D04-B01A-45A4-AEC7-41F91B24DBD7 V1 EN
Figure 507:
Capability curve of a synchronous generator
UEXPDIS protects the synchronous machines against an unstable operation due to
loss of excitation. A partial or total loss of excitation causes a reactive power intake
from the network to the machine, and the reactance of the system viewed from the
machine terminals turns negative. This kind of drop-of-reactance condition can be
detected by measuring the impedance of the system.
The operating characteristic is an offset-mho circle in the impedance plane, and the
circle is parameterized with the Offset, Diameter and Displacement setting values.
Table 869:
Parameters of the circle
Setting values
Description
Offset
Distance of the top of the circle from the R-axis. This is usually set equal to - x
where x
determines the top of the circle regarding the R-axis. If the sign is negative, the
circle lies below the R-axis.
Diameter
Normally set equal to the machine's synchronous reactance x
the size of the impedance circle.
Displacement
Displacement of the center of the circle from the reactance axis or the R-coordinate
of the center. The setting can be used to adjust the sensitivity of the underexcitation
protection. If the sign of the setting is positive, the circle is shifted to the right, that
is, closer to the normal operating point. Respectively, if the sign is negative, the
circle is shifted to the left and thus moves away from the normal operating point.
Generator
B
o
37
o
0.8
1.0
18
C
H
Where,
AB= Field current limit
BC= Stator current limit
CD= End region heating limit of stator. Due to leakage flux
BH= Possible active power limit due to turbine output power limitation
EF= Steady -state limit without AVR
' is the transient reactance of the machine. The sign of the setting value
d
Section 4
Protection functions
P (Active power) p.u.
X
=0.2
e
F
X
=0.0
s
, which determines
d
'/2,
d
937