Section 5
Protection related functions
5.10.4
1140
The directional comparison unblocking scheme DCUB can also be implemented by
complementing the permissive schemes with an additional logic called the unblocking
function, which is also included in DSOCPSCH.
If the permissive overreach scheme is used, some of the power system conditions
require additional special logic circuits, such as the current reversal and weak-end
infeed logic function CRWPSCH.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
The operation of DSOCPSCH can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
CR_PRM
CR_BLOCKING
CR_INTER_TR
CRG
BLOCK
CSUR
CACC
BLK_CS_OPR
CSOR
CSBLK
GUID-1C6DD874-2530-4878-9C02-99A339282B44 V1 EN
Figure 616:
Functional module diagram
The applied communication scheme logic in DSOCPSCH is selected with the Scheme
type setting.
Multiplexer
OR
DCUB
DUTT
OR
PUTT
AND
AND
POTT
OR
DCB
1MRS759142 C
CRL
LCG
CS_INTER_TR
CS_PRM
OPERATE
CS_BLOCKING
REX640
Technical Manual