Section 10
Power quality measurement functions
10.3.6
1632
Voltage swell set
Voltage dip set
Voltage Int set
ST_A
ST_B
ST_C
SWELLST
DIPST
INTST
SWELLOPR
DIPOPR
INTOPR
ST_A
ST_B
ST_C
SWELLST
DIPST
INTST
SWELLOPR
DIPOPR
INTOPR
GUID-DF636037-CE7A-405D-8907-82A96F70CEC6 V1 EN
Figure 843:
Concurrent dip and two-phase swell

Recorded data

Besides counter increments, the information required for a later fault analysis is stored
after a valid voltage variation is detected.
Recorded data information
When voltage variation starts, the phase current magnitudes preceding the activation
moment are stored. Also, the initial voltage magnitudes are temporarily stored at the
variation starting moment. If the variation is, for example, a two-phase voltage dip, the
voltage magnitude of the non-active phase is stored from this same moment, as shown
in
Figure
844. The function tracks each variation-active voltage phase, and the
U_A
U_C
U_B
A) Three phase mode
B) Single phase mode
1MRS759142 C