Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.11.12
REX640
Technical Manual
Name
Type
BASYMM_REF
FLOAT32
GASYMM_REF
FLOAT32
BCOIL
FLOAT32
GCOIL
FLOAT32
BFIXCOIL
FLOAT32
GFIXCOIL
FLOAT32
GPARALLEL
FLOAT32
I_COIL_HMI
FLOAT32
I_COIL
FLOAT32
CALIB_O_MIN
FLOAT32
CALIB_O_MAX
FLOAT32
PASANCR
Enum

Technical data

Table 1437:
PASANCR Technical data
Characteristic
Measuring accuracy
1)
Operation accuracy
1) Network resonance point voltage must be at least 0.01 × U
voltage
Values (Range)
Unit
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
-1000.000...1000
mS
.000
0.00...10000.00
A
0.00...10000.00
A
0...3000
ohm
0...3000
ohm
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Resistance:
±2% or ±1 Ω
I_RESONANCE:
Typically ±2 A
I_DAMPING:
Typically ±2 A
, where U
n
Section 9
Control functions
Description
Reference value of
symmetrical
conductance of network
Reference value of
asymmetrical
susceptance of network
Coil susceptance
Coil conductance
Fixed parallel coil
susceptance
Fixed parallel coil
conductance
Parallel resistor
conducatance
Coil current value
dedicated for HMI
purposes (depends on
Resonance curve Cur
setting)
Adjustable arc
suppression coil value
Low end switch position
of the coil (ohms)
High end switch position
of the coil (ohms)
Status
= nominal phase-to-earth
n
1599