Functionality - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 9
Control functions
9.1.3
9.1.4
1352

Functionality

CBXCBR, DCXSWI and ESXSWI are intended for circuit breaker, disconnector and
earthing switch control and status information purposes. These functions execute
commands and evaluate block conditions and different time supervision conditions.
The functions perform an execution command only if all conditions indicate that a
switch operation is allowed. If erroneous conditions occur, the functions indicate an
appropriate cause value. The functions are designed according to the IEC 61850-7-4
standard with logical nodes CILO, CSWI and XSWI/XCBR.
The circuit breaker, disconnector and earthing switch control functions have an
operation counter for closing and opening cycles. The counter value can be read and
written remotely from the place of operation or via LHMI.
Operation principle
Status indication and validity check
The object state is defined by two digital inputs, POSOPEN and POSCLOSE, which
are also available as outputs OPENPOS and CLOSEPOS together with the OKPOS
according to
Table
1299. The debouncing and short disturbances in an input are
eliminated by filtering. The binary input filtering time can be adjusted separately for
each digital input used by the function block. The validity of the digital inputs that
indicate the object state is used as additional information in indications and event
logging. The reporting of faulty or intermediate position of the apparatus occurs after
the Event delay setting, assuming that the circuit breaker is still in a corresponding
state.
Table 1299:
Status indication
Input
POSOPEN
POSCLOSE
1=True
0=False
0=False
1=True
1=True
1=True
0=False
0=False
Enabling and blocking
CBXCBR, DCXSWI and ESXSWI have an enabling and blocking functionality for
interlocking and synchrocheck purposes.
Circuit breaker control CBXCBR
Normally, the CB closing is enabled (that is, CLOSE_ENAD signal is TRUE) by
activating both ENA_CLOSE and SYNC_OK inputs. Typically, the ENA_CLOSE
Status
Output
POSITION
OKPOS
(Monitored
data)
1=Open
1=True
2=Closed
1=True
3=Faulty/Bad
0=False
(11)
0=Intermediat
0=False
e (00)
1MRS759142 C
OPENPOS
CLOSEPOS
1=True
0=False
0=False
1=True
0=False
0=False
0=False
0=False
REX640
Technical Manual