Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.12.2.10
1032
Name
Type
COUNT_BR2_A
INT32
COUNT_BR1_B
INT32
COUNT_BR2_B
INT32
COUNT_BR1_C
INT32
COUNT_BR2_C
INT32
FAIL_COUNT
INT32
CUBPTOC
Enum
I-unb-xIn:1
FLOAT32

Technical data

Table 972:
CUBPTOC Technical data
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Operate time accuracy in definite time mode
Operate time accuracy in inverse definite
minimum time mode
Suppression of harmonics
1) Fundamental frequency current = 1.0 × I
value , results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Values (Range)
Unit
0...2147483647
0...2147483647
0...2147483647
0...2147483647
0...2147483647
0...2147483647
1=on
2=blocked
3=test
4=test/blocked
5=off
0.00...5.00
xIn
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
1.5% of the set value or 0.002 × I
Typically 26 ms
Typically 40 ms
Typically 0.96
1% of the theoretical value or ±20 ms
5% of the theoretical value or ±20 ms
DFT: -50 dB at f = n × f
, current before fault = 0.0 × I
n
1MRS759142 C
Description
Number of element
failures in branch2
phase-A
Number of element
failures in branch1
phase-B
Number of element
failures in branch2
phase-B
Number of element
failures in branch1
phase-C
Number of element
failures in branch2
phase-C
Total number of element
failures
Status
Measured neutral
unbalance current
amplitude
n
, where n = 2,3,4,5,..
n
Start
, fault current = 2.0 ×
n
REX640
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents