Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.3.7.5
704
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of MPDIF can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
I_A1
I_B1
I3P1
I_C1
I_A2
I_B2
I3P2
I_C2
BLOCK
BLK_OPR_LS
BLK_OPR_HS
GUID-E0FE531A-37D4-45A8-9B9A-C9C4C113A307 V1 EN
Figure 390:
Functional module diagram
Differential and bias calculation
Differential calculation module calculates the differential current. The differential
current is the difference in current between the phase and neutral sides of the machine.
The phase currents
and
I
1
phase and neutral sides of the current. The amplitude of the differential current I
obtained using the equation (assuming that the positive direction of the current is
towards the machine):
Differential
and bias
calculation
Through
Instan-
fault
taneous
detection
high stage
DC
Biased low
component
stage
detection
CT
saturation
based
blocking
denote the fundamental frequency components on the
I
2
1MRS759142 C
OPERATE
OPR_LS
OPR_HS
INT_BLKD
is
d
REX640
Technical Manual